Line Volume per Length: Solvent Holdup in Stainless Tubing

How much liquid a run of tube holds, from its inside diameter, in gallons, liters and pounds of solvent.

DocumentREF-LV-01
SeriesEngineering Reference
Revision2026.1
Issued24 September 2026
Use this sheet to account for solvent sitting in transfer lines, to size a system charge, and to estimate how much solvent is trapped between two valves.

Internal volume by tube size

Tube OD Wall (in) ID (in) in³ per ft gal per 10 ft L per m Butane lb / 10 ft Propane lb / 10 ft 75/25 lb / 10 ft 50/50 lb / 10 ft
1/4" 0.035 0.180 0.31 0.013 0.016 0.06 0.06 0.06 0.06
3/8" 0.035 0.305 0.88 0.038 0.047 0.18 0.16 0.18 0.17
1/2" 0.065 0.370 1.29 0.056 0.069 0.27 0.24 0.26 0.25
3/4" 0.065 0.620 3.62 0.157 0.195 0.76 0.66 0.74 0.71
1" 0.065 0.870 7.13 0.309 0.384 1.50 1.30 1.45 1.40
1-1/2" 0.065 1.370 17.7 0.766 0.951 3.73 3.23 3.60 3.48
2" 0.065 1.870 33.0 1.43 1.77 6.95 6.02 6.72 6.48
2-1/2" 0.065 2.370 52.9 2.29 2.85 11.2 9.67 10.8 10.4
3" 0.065 2.870 77.6 3.36 4.17 16.4 14.2 15.8 15.3
4" 0.083 3.834 138.5 6.00 7.45 29.2 25.3 28.2 27.3
6" 0.109 5.782 315.1 13.64 16.94 66.4 57.6 64.2 62.0
8" 0.109 7.782 570.8 24.71 30.69 120.3 104.3 116.3 112.3

Walls are the standard sanitary and instrument walls used on N.B. Oler systems. Solvent weights are liquid full values at 60°F (16°C): butane 4.87 lb/gal, propane 4.22 lb/gal; blends by liquid volume. Colder liquid is denser, see REF-SC-01.

Formulas

  • Inside diameter: ID = OD - 2 x wall.
  • Volume per foot: in³/ft = (π / 4) x ID² x 12. Gallons = in³ / 231. Liters = in³ x 0.016387.
  • Solvent holdup: lb = gallons x liquid density. For a section trapped between two closed valves, use the length between the valve seats and add the valve body volume.
  • Hose and fittings. Hose ID often differs from tube ID of the same nominal size. Use the hose maker's ID, and add tee, cross and valve volumes when a line has many fittings.
Trapped liquid is a hazard. Liquid locked between two closed valves builds pressure quickly as it warms. A 10 ft liquid full section of 1 inch line holds about 1.5 lb (0.7 kg) of butane. Never close both ends of a liquid full line without a relief path.

Sources. Tube dimensions per ASTM A269/A270 standard walls. Densities from NIST Chemistry WebBook saturated liquid data at 60°F (16°C), as used in REF-SC-01.